Old School Lab Testing & a Need for Change
Oil-filled test terminations have been the go-to solution for laboratory tests but topped out at 100kV AC, introducing fluid, fireload, and changeover issues for every test sequence. Air-insulated assemblies have practical limits around 36kV. Above 100kV AC the test fixture is often the limiter -- either you create too much nuisance discharge due to poor field stress at the tester connection or set-up/tear down time cuts into the already long day-and-a-half for an IEC60840 type test’s heat-cycle part.
A water-filled cable test termination system removes that interface as a variable. Deionized water sits at a relative permittivity close to crosslinked polyethylene (about 80 versus XLPE's 2.3), so the electric field grades smoothly along the cable end rather than concentrating at a knife edge. With a closed-loop CTW conditioning unit holding the water conductivity in the 0.1–2 µS/cm window and the temperature stabilised, DEMIKS water-filled CTTS systems hold partial discharge below 1 pC up to 400 kV AC and below 2 pC at 500–800 kV — the same performance band the IEC 60840 acceptance limit of 5 pC for new installations is designed to leave headroom on.