DC Withstand Voltage Calculator — IEC 60840 / IEC 60229

Compute the required DC test voltage, test duration and leakage threshold for cable accessory acceptance (IEC 60840, ≤150 kV) or cable sheath integrity (IEC 60229 / IEEE 400). Then size the required DEMIKS HVDC system. Inputs follow the published standards; the result is directional and must be cross-checked against the project specification.

Your inputs

Select the workload that matches your project
Example: 66 kV system → Uo ≈ 38 kV; 110 kV system → Uo ≈ 64 kV
IEC 60840 :2020 recommends 1.73 or 2.0 × Uo for after-installation tests
Cable + termination + DUT combined capacitance
µA-level for dry insulators; mA-level for long cables
Standard 1–2 kV/s; slow near target voltage

Enter parameters and click Calculate to generate sizing data.

Calculated Sizing

Required DC Test Voltage
0.0 kV
Minimum Generator Rating (≥ 1.2× Rule)
0 kV
Ramp Time
0 s
Test Duration
15 min
Max Leakage Threshold
0.5 mA