Fraud Blocker

Why PD Diagnostics Are Difficult to Interpret — and How to Read Them Correctly

Partial discharge (PD) diagnostics – measuring small regions of dielectric failure within high-voltage equipment including cables, transformers, switchgear, motors, and generators – can be extremely tricky to understand. One off value can mark an otherwise sound equipment as faulty, or go unnoticed for weeks before ultimately causing serious hardware failure. Despite more than 15,000 machines equipped with permanent PD sensors across the world and over 400,000 readings stored in the international database documented in the CIGRE 2016 study by Sedding, Stone and Warren, many plants find it difficult to produce consistent, reliable diagnostic assessments.

This guide unpacks the four hidden axes that make PD interpretation hard — sensor bias, asset baseline, noise contamination, and pattern ambiguity — and gives you a working framework to read PD results like an experienced HV test engineer.

Quick Specs

What PD is Localized insulation breakdown that does not bridge the full electrode gap
Typical voltage range 3 kV to 700 kV and beyond
Governing standards IEC 60270 (off-line, charge-based) · IEC 60034-27-2 (on-line, rotating machines) · IEEE 1434 (rotating-machine PD guide)
Primary measurement units pC (picocoulombs, IEC 60270) or mV (on-line, wide-band)
Top 3 sources of interpretation error Noise contamination · sensor-type bias · asset-baseline mismatch

Why “Easy-to-Read” PD Reports Are Often Wrong

Why "Easy-to-Read" PD Reports Are Often Wrong

A PD report may appear reassuringly numeric — a Qm of 240 mV, an apparent charge of 12 pC, a pristine phase-resolved plot — but still lead you astray. What appears on the page is the result of at least four separate variables, any of which can mask or fake your reading: the sensor and its bandwidth, the asset class and its statistical norms, the noise environment around the test setup, and the discharge mechanism itself.

If the report neglects any of the above axes, the two failures are that either an alarm sounds on a “healthy” asset – a false positive that undermines the integrity of the testing regime – or a genuine fault ends up below an inappropriate threshold, so the asset fails in-between scheduled tests. As noted by field engineer “jburn” in a long-running Eng-tips exchange following his first commercial PD survey: “It does take a highly skilled engineer or technician to interpret the data as it is being taken.”

⚠️ Important

PD test interpretation is a four-axis decision: sensor / asset / noise / pattern. A confident-looking single number that neglects any of these four axes is more hazardous than having no number at all.

PD Fundamentals: What You Are Actually Measuring

PD Fundamentals: What You Are Actually Measuring

A partial discharge is a flashover of a specific section of an insulation system which has an electric field gradient that is below the dielectric withstand level of the target section ( with the entire system still being able to sustain the applied electric field). Every flashover results in a high frequency pulse of current, as well as several observable consequences: light, heat, ozone, audible crackling, electromagnetic emissions, an HF earth-current pulse. Each of them can be detected with different types of sensors, as each reveals something slightly different about the defect.

Field practice divides PD into three families. Correct classification matters because each family produces a different PRPD signature, prefers a different sensor, and carries a different failure-rate profile.

PD type Where it happens Best primary sensor Pre-failure warning
Internal PD Voids, cavities, gaps inside solid insulation; gas-filled defects within cast resin or polymer TEV (switchgear); HFCT / 80 pF coupler (cables, transformers) Often silent — no smell, sound, or visible sign before failure
Surface PD Tracking across the surface of insulation, often at dry terminations or interfaces Airborne ultrasonic; contact ultrasonic for sealed enclosures Ozone smell, audible crackling, eventual surface erosion
Corona PD Sharp electrode geometry discharging into a gas (typically air, occasionally SF6 anomalies) UHF; airborne ultrasonic in open switchyards Visible blue glow in dark; audible hissing in humid weather
📐 Engineering Note — The Smell-Sound-Spark Audit

Before any meter ever gets installed on a substation, do a sensory walkdown. Ozone smell from a locked cabinet suggests surface PDs are active inside; loud crackling from switchgear gaskets suggests huge internal or surface activity; dead sometimes-visible corona at sharp edges on the outside is usually not an asset life issue but can initiate surface PD inside closed chambers if airflow is tight. Three minutes of sensory triage can tell you which sensor to put on first.

How Sensor Choice Biases Your Interpretation

How Sensor Choice Biases Your Interpretation

Two PD sensors on the same fault rarely give the same number. That is not measurement error, it is physics.

Each sensor type has its own bandwidth, coupling mechanism and frequency response, and each its own failure mode blind spots. Pick the wrong sensor and the report you generate is internally consistent but externally wrong.

Sensor Physical principle Best-fit fault Interpretation caveat
80 pF capacitive coupler Phase-terminal HV capacitor sensing pulse current Stator winding (motors, generators); transformer terminals Sensitivity drops for coils deep in the winding away from line terminals
Stator slot coupler (SSC) Antenna under slot wedges, picks up local slot PD Hydrogen-cooled turbogenerators where 80 pF couplers struggle Local-only — does not see endwinding or terminal PD
TEV (Transient Earth Voltage) HF EM pulses leaving switchgear through gasket openings Internal PD inside metal-clad switchgear Cannot localize to a specific cubicle without scanning multiple positions
HFCT / RFCT Clip-on current transformer on cable earth lead On-line MV/HV cable PD without taking the cable out of service Picks up everything on the earth conductor — needs noise discrimination upstream
UHF Antenna-based EM detection in the 300 MHz to 3 GHz band GIS, open switchyards, cable systems where contact sensors are impractical Sensitivity depends on antenna placement and shielding geometry
Ultrasonic (airborne / contact) Acoustic emissions in the ultrasonic band, often dropping into audible range as severity grows Surface PD and corona PD with an air path or contact path to the source Misses sealed internal PD; sensitive to ambient acoustic noise

Bandwidth merits its own note. Sensors operating above about 40 MHz pick up the first peak of a PD pulse as a traveling wave, prior to the inductance and capacitance of the winding distorting it. According to the Iris Power CIGRE study quoted above, that is why high frequency on-line measurements on stators behave as roughly absolute values -the meter does not see the full stator impedance loop.

Low bandwidth measurements, on the other hand, see a heavily filtered pulse, and the absolute value depends strongly on coil geometry. Cross machine comparison in a single sensor bandwidth domain only makes sense.

When you need one field instrument that covers the full sensor family, and all that family shares trending software, look at integrated professional high voltage test equipment rather than single-sensor units that leave you trapped into one interpretation model.

Asset-Type Acceptance Baselines and Why Cross-Asset Comparison Fails

Asset-Type Acceptance Baselines and Why Cross-Asset Comparison Fails

A Qm of 250 mV on a 13.8 kV air-cooled turbogenerator is innocuous; the same number on a hydrogen-cooled machine at 30 psig is a strong fault investigation trigger; on an oil-filled transformer it is meaningless because the instrument was probably operating in the wrong scale. PD thresholds are asset-class-specific, and you should read any rule you import from another asset class as an authoritative “rule of thumb” that will mislead you.

Reference baselines by asset class

Asset class Typical method Units Investigation trigger Standard
13.8 kV air-cooled stator (TGA) On-line, 80 pF coupler mV (wide-band) Qm above 90th percentile (about 529 mV per Iris dataset) IEC 60034-27-2 · IEEE 1434
Hydrogen-cooled stator (>30 psig) On-line, 80 pF coupler or SSC mV (wide-band) 90th percentile typically near 250 mV — about half the air-cooled threshold IEC 60034-27-2 · IEEE 1434
MV oil-filled transformer Off-line factory test; HFCT on-line in service pC (off-line); mV (HFCT on-line) Acceptance values defined by purchase spec; consensus rejection above 100 pC at 1.5 U0 IEC 60270 · IEC 60076-3
XLPE MV cable Off-line VLF or damped-AC at 1.5 to 2.0 U0; on-line HFCT pC (off-line, IEC 60270 charge-calibrated) Any detectable PD at electrical-tree signature is significant — typical remaining life: hours to days IEC 60270 · IEEE 400.4
MV metal-clad switchgear On-line TEV plus ultrasonic survey dB (TEV); dB (ultrasonic) TEV consistently above 20 dB or rising; any audible ultrasonic activity IEC TS 62478
📐 Engineering Note — Cooling medium changes the baseline by a factor of two

Hydrogen-cooled machines consistently demonstrate lower PD magnitudes than air-cooled machines of equivalent kV rating, because the higher dielectric strength of pressurized hydrogen raises the inception voltage of bulk insulation flaws. Per the Iris on-line PD database, the 90th-percentile Qm at higher H2 pressures drops to roughly half the air-cooled value. Comparing any hydrogen-cooled reading against an air-cooled threshold table is a mistake because gas-gap geometry dominates the result.

One helpful field observation: when “kraigb” of a North American utility scheduled their MV underground distribution at 1.5 to 2.0 per-unit voltage, the ratio of PD “hits” in cable accessories – splices, terminations, elbows – versus the cable itself was far higher than the 4:1 accessory-to-cable failure ratio in service. Insulation degradation from workmanship errors at the accessory connection point, rather than bulk cable insulation failure, was the source of most of the PD activity they observed. Baselines drawn from cable manufacturer specifications seldom account for that — adjust your expectations if the survey is accessory-heavy.

PRPD Patterns: Reading the Phase-Resolved Plot

PRPD Patterns: Reading the Phase-Resolved Plot

Phase resolved partial discharge (PRPD) plotting is by far the most useful aid to interpretation, as well as the easiest to abuse. Every individual pulse is plotted a 2D plot of the AC phase angle (x-axis, 0 – 360 degrees) and the pulse amplitude (y-axis). Watch the same defect long enough and a identifiable cloud is created – the shape of the cloud identifies the class of defect firing.

The 4-Pattern PRPD Checklist for Field Triage


  • Internal void (bulk insulation): Roughly equal cloud density on both positive and negative half-cycles, centered around 45 and 225 degrees. Magnitudes cluster tightly. Pulse polarity symmetry is the giveaway.

  • Surface PD (delamination or interface tracking): Asymmetric pattern — more activity on one polarity than the other. Cloud spreads broadly along the rising voltage edge. Often paired with audible crackling and ozone smell.

  • Corona PD (sharp electrode in gas): Tight, repeatable pulse population at one phase angle, almost always positive half-cycle. Magnitudes are uniform and low. Often suppressed by humidity changes.

  • Floating-metal or poor contact: Sparse, very-high-magnitude pulses at low repetition rate, often at non-canonical phase angles. The signature looks chaotic compared to the other three — that chaos is the diagnosis.

Polarity indicates the void location. As one experienced motor-industry engineer (“electricpete”) summarized in a long-running Eng-Tips practitioner thread on PD interpretation: positive pulses dominating implies voids on the outer wall of the insulation (between the insulation and the ground plane), negative pulses dominating implies voids on the inner wall (between the insulation and the energized conductor), and roughly equal positive plus negative populations implies voids in the insulation bulk. That single polarity check, taken before any magnitude analysis, often resolves whether a borderline reading deserves an outage or another six months of monitoring.

“We have tested in excess of 10,000km of MV cable globally, and I can count the voids we have encountered on one hand. Academics love a good theory about them as much as they do their beautiful mathematics, but in reality they are an issue of exceedingly low probability. In virtually all the aged cable PD studies I have been involved with, an electrical tree was found close to a water tree.”

— senior cable PD test engineer, Eng-Tips practitioner forum

This field reality contradicts the boilerplate statement about Cable PD, and should cause caution when interpreting a cable plot. If your pattern shows the broad, asymmetric cloud of moisture-driven tree development rather than the narrow internal-void signature, you are almost certainly looking at a water-tree-to-electrical-tree progression rather than a manufacturing void — and the remaining service life is measured in days, not years.

Noise Discrimination: The Number-One Source of False Alarms

Noise Discrimination: The Number-One Source of False Alarms

Interference is the largest single factor of false PD interpretation. The same OMICRON white-paper on noise suppression describes the 3PARD principle thusly: “External disturbance often dominates the PD signal, so the apparent charge value indicated by the measurement system in accordance with IEC 60270 is increased compared with the real apparent charge value from the test object.” If the noise level exceeds that of the signal, the test measures the noise, not the PD.

This can be very costly plants, through over-buying on false alarms. As an electrical engineer described by a 13.8 kV 30-machine group of similar installation: “Approximately 50% of the machines report a level higher than the predetermind warning point set by the vendor.” When this makes half your false alarms, operational personnel ignore the reports – allowing the one real alarm next month to go unnoticed.

Noise sources you will encounter

Noise source Typical PRPD signature Best discriminator
Power-system corona Pulses concentrated at peak voltage; suppressed by humidity rise Phase-window gating; 3PARD geometry filter
Slip-ring or commutator sparking Random across cycle; modulated by rotor speed Cross-correlate with shaft speed; time-of-flight separation
Inverter / VFD switching Periodic 6-pulse cluster at fixed phase positions Channel gating from a coupling near the inverter
Mobile radio / cell-tower RF Burst noise unrelated to AC cycle; specific frequency band 3FREQ / 3CFRD frequency-signature filtering
Electrostatic precipitator High-amplitude impulses, irregular firing Window gating in phase and amplitude

Two analytical techniques published by OMICRON have become de facto field standards for noise-vs-PD separation. 3PARD — the 3-Phase Amplitude Relation Diagram — uses synchronous three-phase measurement and projects all pulses onto a single star diagram so that genuine internal PD (which is phase-correlated) separates visibly from noise (which is not). 3FREQ, also called 3CFRD, applies three digital filters at different centre frequencies to a single channel and characterises each pulse by its frequency signature, so corona, inverter noise, and true PD form distinct clusters even when only one phase is instrumented. Both methods turn noise-vs-PD discrimination from a heuristic exercise into a graphical decision.

💡 Pro Tip

Prior to any PD survey, construct a reference trace with the test article de-energized, sensors installed, quite. That becomes the noise reference – anything present with power off will be noise; anything only appearing in the energized trace is a PD candidate.

Which Standard Applies? IEC 60270 vs IEC 60034-27-2 vs IEEE 1434

Which Standard Applies? IEC 60270 vs IEC 60034-27-2 vs IEEE 1434

Three documents dominate most PD acceptance decisions, and they scarcely overlap as titles and maturities suggest. Use the wrong one and you find yourself applying the wrong off-line acceptance criteria on on-line data, or relating rotating machine results to an apparatus standard that was never intended for stator windings.

Standard Scope On/Off-line Units Acceptance approach
IEC 60270 (latest edition 2025) Charge-based PD measurement on HV apparatus generally Primarily off-line / factory pC, charge-calibrated against a reference impulse Test-specification driven; the product standard sets pass/fail
IEC 60034-27-2 On-line PD on the stator winding insulation of rotating electrical machines On-line, in normal operation mV (wide-band) or pC (where calibration is feasible) Trend-based; comparative against similar machines and prior measurements
IEEE 1434 (2014) Guide for the measurement of PD in AC electric machinery On-line and off-line guidance mV most commonly Statistical, requires stable operating conditions for valid trending
📐 Engineering Note — pC and mV are not interchangeable on rotating machines

Reporting on-line stator PD in pC implies an IEC 60270 charge calibration that is generally not achievable on a complete winding, because the inductive and capacitive load of the stator distorts the calibration pulse. Per the CIGRE 2016 Iris Power study, on-line stator pulse magnitudes are measured in mV “rather than picoCoulombs, due to the difficulty in calibrating into pC.” If a report mixes the two units on the same machine, treat the numbers with caution.

A Decision Framework for a Single PD Reading

A Decision Framework for a Single PD Reading

Most field technicians can only react to a single reading at a time, and usually without the advantage of months of trend. The “4-Step Single-Reading Triage” below is derived from Iris Power statistical research plus the accumulated practitioner consensus on Eng-Tips and similar forums over twenty years. It is no substitute for trend; but it is a defendable action when a trend is not available.

The 4-Step Single-Reading Triage
  1. Normalize to asset-class. Transform the raw reading into a percentile against an asset-class dataset of the same voltage, cooling method, and sensor type. The Iris dataset establishes that readings above the 90th percentile have historically correlated with confirmed insulation deterioration in more than 200 visually inspected cases.
  2. Discriminate noise. Replay the measurement with channel gating, 3PARD, or 3FREQ active. If the value falls by more than 6 dB after filtering, the original was at least half noise. Re-trigger the threshold check against the filtered value.
  3. Classify the pattern. Match the dominant PRPD signature against the 4-Pattern Checklist above. Internal-void and surface PD signatures justify investigation; corona alone usually does not. Floating-metal patterns demand an outage — they progress quickly.
  4. Action selection. If steps 1 to 3 all clear (under 90th percentile, no filtered-noise drop, corona-only pattern), continue normal monitoring. If any one fires red, schedule the corresponding follow-up: comparative off-line PD test at 1.5 to 2.0 per-unit voltage for cables and bushings, visual inspection at the next outage for stators, accelerated re-test within 30 days for any borderline switchgear.

A note on operating-voltage limits: as one Eng-Tips contributor with a 10,000 km cable test history noted, “3% or less PD sites will show up at operation voltage” — most cable insulation defects do not discharge at nominal voltage, so on-line testing alone systematically misses them. When the cost of a missed flaw is outage, plan to follow up an on-line survey with an off-line measurement at 1.5 to 2.0 per-unit voltage. Properly equipped Demiks Power high voltage test equipment provides both on-line and off-line capability in one instrument family, which makes the data directly comparable.

2025 to 2026 Outlook: AI-Assisted PD Pattern Interpretation

2025 to 2026 Outlook: AI-Assisted PD Pattern Interpretation

In the past two decades, the biggest change in PD interpretation has been the adoption of image-based deep learning for pattern recognition. A 2025 paper in MDPI Applied Sciences launched TEV-based AI-augmented monitoring using convolutional networks directly consuming the PRPD plot as an image, rather than a vector of extracted features. Similarly, a 2025 indexed at PubMed Central applied CNN and recurrent network architectures to PD signal classification in power transformers, with classification accuracy outperforming traditional support vector machine baselines.

For the asset-owner, two hard facts in 2026 matter. First, the new EN IEC 60270:2025 edition has refreshed the specifications for charge-based PD measurement after a 25-year hiatus – if you specify factory acceptance tests for HV equipment in 2026 or later, reference the 2025 edition rather than the 2000 edition. Second, AI interpretation is already a useful second opinion rather than a blind substitute for an experienced analyst; treat it as a triage tool that marks candidates for human review, not as a black-box pass/fail.

Frequently Asked Questions

Q: What is the most common cause of partial discharge in transformers?

View Answer
In oil-filled power transformers, the dominant root causes are moisture ingress into the cellulose paper insulation, gas bubbles around overheated tap-changer contacts, and floating-metal defects from loose hardware that creates a low-grade arc to ground. Each of these produces a distinct PRPD signature that a trained analyst can separate from corona at the bushing terminals — which is normally benign but often dominates the unfiltered PD reading.

Q: What is the acceptable level of partial discharge in MV cables?

View Answer
Factory acceptance for new XLPE MV cable under IEC 60270 typically requires no detectable PD above the noise floor at 1.5 U0 — practically, below 5 to 10 pC after calibration. In service, any detectable PD with an electrical-tree PRPD signature should be treated as urgent: field experience indicates remaining life of hours to days once a discernible tree forms, regardless of absolute magnitude. Cable accessories — splices, terminations, elbows — tolerate slightly higher levels because their composite insulation is more PD-tolerant than extruded cable.

Q: How does on-line PD testing differ from off-line PD testing?

View Answer
On-line testing measures PD at nominal operating voltage while the asset stays in service — fast, non-disruptive, but limited to defects that discharge at U0. Off-line testing applies an external 50 or 60 Hz, VLF, or damped-AC source at elevated voltage (typically 1.5 to 2.0 U0) and exposes defects that stay below the inception voltage at normal operation. The two methods are complementary: on-line surveys are appropriate for continuous condition monitoring, while off-line tests are needed when a baseline is required or when defects sit below the on-line sensitivity threshold.

Q: What does IEC 60270 actually specify?

View Answer
IEC 60270 — refreshed in 2025 as EN IEC 60270:2025 — defines the methodology for charge-based PD measurement on HV apparatus, including the calibration procedure that produces the picocoulomb (pC) value reported on factory acceptance tests. It does not set pass/fail thresholds itself; individual product standards (IEC 60076-3 for transformers, IEEE 400.4 for cables, and others) reference IEC 60270 as the measurement method and add their own acceptance limits.

Q: Can AI accurately interpret PRPD patterns?

View Answer
For known defect signatures with sufficient labelled training data, current convolutional-network approaches reach classification accuracy comparable to experienced human analysts on PRPD images. For novel or composite defects — where two or more discharge mechanisms overlap on the same plot — model performance drops, and human review remains the right path.

About This Analysis

This guide summarizes peer-reviewed CIGRE studies on live PD interpretation for rotating machines, technical whitepapers from OMICRON on noise suppression and PRPD analysis, the IEC 60270, IEC 60034-27-2 and IEEE 1434 standards related to PD measurement, and specialist discussion on the Eng-Tips electrical-engineering forum. It is a working interpretation guide for the benefit of engineers that specify, operate or commission PD testing with high voltage testing instruments. Reviewed by the Demiks Power engineering team.

References & Sources

  1. Progress in Interpreting On-Line Partial Discharge Test Results from Motor and Generator Stator Windings (Sedding, Stone, Warren) — CIGRE 2016, Paris
  2. How to Analyze Partial Discharge — OMICRON electronics GmbH technical whitepaper
  3. Noise Suppression and Source Separation Techniques (3PARD / 3FREQ) — OMICRON electronics GmbH
  4. IEC 60270:2025 — High-voltage test techniques — Charge-based partial discharge measurements — International Electrotechnical Commission
  5. IEC 60034-27-2 — Rotating electrical machines — On-line partial discharge measurements on the stator winding insulation — International Electrotechnical Commission
  6. IEEE 1434-2014 — Guide for the Measurement of Partial Discharges in AC Electric Machinery — Institute of Electrical and Electronics Engineers
  7. AI-Augmented Partial Discharge Analytics for TEV-Based Monitoring — MDPI Applied Sciences, 2025
  8. Research on partial discharge signal recognition and classification using deep learning — PubMed Central PMC12633952, 2025
Scroll to Top
Get in touch with DEMIKS company
Contact Form 在用